bldg |
room |
responsible |
Item of concern |
abatement time |
date corrected |
|
BRWN |
B103 |
Keyes |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. And see Acronyms.xls |
10/28/01 | |
|
BRWN |
B124 |
Hallenga |
Container of chemical is unlabeled. |
10/18/01 | |
|
BRWN |
B125 |
Wenthold |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. |
10 d |
10/10/01 |
|
BRWN |
B125 |
Wenthold |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/10/01 | |
|
BRWN |
B125 |
Wenthold |
Excessive accumulation or abandoned containers of chemical waste. (fume hood A) |
10 d |
10/18/01 |
|
BRWN |
B125 |
Wenthold |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrogen) See note 7. |
10/16/01 | |
|
BRWN |
B125A |
Wenthold |
Container of chemical is unlabeled. |
10/16/01 | |
|
BRWN |
B125A |
Wenthold |
Chemical storage refrigerator(s) and/or freezer(s) should be cleaned and/or organized more safely. |
11/5/01 | |
|
BRWN |
B125A |
Wenthold |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid under fume hood. (CORRECTED at inspection) |
10/3/01 | |
|
BRWN |
B125A |
Wenthold |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/28/01 | |
|
BRWN |
B125B |
Wenthold |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/16/01 |
|
BRWN |
B137 |
Ben-Amotz |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/24/01 |
|
BRWN |
B137 |
Ben-Amotz |
Container of chemical is unlabeled. |
10/31/01 | |
|
BRWN |
B137A |
Ben-Amotz |
Restore minimum aisle width of 22". |
10 d |
10/31/01 |
|
BRWN |
B137A |
Ben-Amotz |
Extension cord used as permanent wiring. Install permanent outlet or use 15-amp maximum fuse/circuit breaker multiple outlet device. |
30 d |
10/24/01 |
|
BRWN |
B137A |
Ben-Amotz |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/24/01 |
|
BRWN |
B137A |
Ben-Amotz |
Alcoholic beverages are stored in this area. |
Immed |
10/24/01 |
|
BRWN |
B144 |
Morris (Zone 1) |
Ensure compressed air regulator nozzles for cleaning are limited to 30 PSI. |
60 d |
11/16/01 |
|
BRWN |
B144 |
Morris (Zone 1) |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. |
10 d |
11/5/01 |
|
BRWN |
B144 |
Morris (Zone 1) |
Container of chemical is unlabeled. (coffee can used secondary storage container) |
11/5/01 | |
|
BRWN |
B144 |
Morris (Zone 1) |
Workplace not reasonably free of recognized hazards. Ensure barriers across dropoffs are in place. [Corrected at inspection] |
10 d |
10/2/01 |
|
BRWN |
B147 |
McLuckey |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/19/01 |
|
BRWN |
B151 |
Wenthold |
Excessive fire fuel loading (paper and/or other combustibles). Remove empty box storage. |
11/7/01 | |
|
BRWN |
B155A |
McLuckey |
Power cord damaged or broken. Electrical tape is unacceptable. (Oven) |
10 d |
10/22/01 |
|
BRWN |
B155A |
McLuckey |
Chemical storage refrigerator(s) and/or freezer(s) should be cleaned and/or organized more safely. |
10/23/01 | |
|
BRWN |
B155A |
McLuckey |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/3/01 | |
|
BRWN |
B155A |
McLuckey |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/24/01 | |
|
BRWN |
B155A |
McLuckey |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
10/24/01 | |
|
BRWN |
B165 |
Francisco |
Container of chemical is unlabeled. |
11/14/01 | |
|
BRWN |
B165 |
Francisco |
Chemical containers have labels that are deteriorating and/or unreadable. |
11/14/01 | |
|
BRWN |
B165 |
Francisco |
Power cord damaged or broken. Electrical tape is unacceptable. (on vacuum pump) |
10 d |
11/29/01 |
|
BRWN |
B165 |
Francisco |
Electrical cord tunnels across aisleways are not acceptable. |
30 d |
11/14/01 |
|
BRWN |
B165 |
Francisco |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid. |
11/14/01 | |
|
BRWN |
B165A |
Francisco |
Container of chemical is unlabeled. |
||
|
BRWN |
B165A |
Francisco |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/14/01 |
|
BRWN |
B165B |
Francisco |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/14/01 |
|
BRWN |
B171B |
Daly |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/23/01 LAS |
|
BRWN |
B175 |
Zwier |
Food stored with laboratory equipment and/or chemicals. |
10/31/01 | |
|
BRWN |
B175 |
Zwier |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. |
10 d |
10/31/01 |
|
BRWN |
B175 |
Zwier |
Open chemical containers not in use (pump oil). (CORRECTED at inspection) |
10/3/01 | |
|
BRWN |
B175 |
Zwier |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Remove cords from across aisleway. See note 8. |
11/20/01 ramp plan approved by Don Campbell | |
|
BRWN |
B175 |
Zwier |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (acetylene) See note 7. |
10/31/01 | |
|
BRWN |
B175B |
Zwier |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/20/01 |
|
BRWN |
B178 |
McLuckey |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/3/01 | |
|
BRWN |
B178 |
McLuckey |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. See note 8. |
10/17/01 | |
|
BRWN |
B178 |
McLuckey |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/24/01 | |
|
BRWN |
B178 |
McLuckey |
Container of chemical is unlabeled. (pump oil) |
10/19/01 | |
|
BRWN |
B178 |
McLuckey |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/22/01 |
|
BRWN |
Basement Corridor |
Dirksen |
Corridor obstructed. Remove equipment and other items stored in corridor. |
10 d |
12/6/01 |
|
BRWN |
1124 |
Keyes |
Possible potable water supply cross connection exists. (In hood.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
1124B |
Keyes |
Restore room fire resistivity - patch holes through walls or floor. |
30 d |
11/19/0 |
|
BRWN |
1125 |
Keyes |
Possible potable water supply cross connection exists. (In hoods.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
1134 |
Keyes |
Possible potable water supply cross connection exists. (In hood.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
1135 |
Keyes |
Possible potable water supply cross connection exists. (In hoods.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
1152B |
Iota Sigma Pi |
Restore housekeeping. |
10 d |
11/8/01 |
|
BRWN |
1152B |
Iota Sigma Pi |
Excessive fire fuel loading (paper, cardboard and/or other combustibles). |
11/8/01 | |
|
BRWN |
1155 |
Keyes |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid under the fume hood. |
10/22/01 | |
|
BRWN |
1165 |
Keyes |
Possible potable water supply cross connection exists. (In hood.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
1182 |
Bldg Srvcs (will be taken care of by F. Salazar) |
Excessive fire fuel loading -- plastic, cardboard and/or other combustibles stuffed into Northwest corner. See note 10. |
10/23/01 as per F. Salazar email | |
|
BRWN |
2150 |
Safety, First Aid |
Replace box of gloves in First Aid room. |
11/16/01 | |
|
BRWN |
2150 |
Safety, First Aid |
Air purifying respirators ("gas masks") are not permitted in laboratories unless lab staff are a part of the Purdue Respiratory Protection Program. Two cases with gas mask components were removed. (CORRECTED by REM at inspection) |
(10/2//01) | |
|
BRWN |
2164 |
Keyes |
Possible potable water supply cross connection exists. (In hoods.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
2164 |
Keyes |
Restore room fire resistivity - patch holes through walls or floor. (Remove nitrogen line from hole drilled through wall between small storage room and lab.) |
30 d |
11/19/0 |
|
BRWN |
2174 |
Keyes |
Restore room fire resistivity - patch holes through walls or floor. (Remove nitrogen line from hole drilled through wall between small storage room and lab.) |
30 d |
11/19/0 |
|
BRWN |
2174 |
Keyes |
Possible potable water supply cross connection exists. (In hoods.) see note 1. |
1 year |
11/10/0 |
|
BRWN |
2174C |
Keyes |
Excessive accumulation or abandoned containers of chemical waste. Waste totalling 30+ gallons. |
10 d |
10/28/01 |
|
BRWN |
2182 |
Keyes |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/28/01 (moved liquids down) |
|
BRWN |
2184 |
Keyes |
Restore aisleway. Remove bulletin board, fan, and cardboard box. |
10 d |
10/22/01 |
|
BRWN |
3107 |
Biology |
Container of chemical is unlabeled. |
11/5/01 | |
|
BRWN |
3107B |
Biology |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/15/01 |
|
BRWN |
3107B |
Biology |
Container of chemical is unlabeled. |
11/5/01 | |
|
BRWN |
3107B |
Biology |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
11/8/01 |
|
BRWN |
3107B |
Biology (emailed Mason and Browning 10/26) |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/15/01 |
|
BRWN |
3107B |
Biology |
Power cord damaged or broken. Electrical tape is unacceptable. (Fisher hotplate/stirrer) |
10 d |
11/15/01 |
|
BRWN |
3124 |
Hrycyna |
Eyewash and/or shower is obstructed. See note 8. |
10/22/01 | |
|
BRWN |
3124 |
Hrycyna |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/22/01 | |
|
BRWN |
3124 |
Hrycyna |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/22/01 | |
|
BRWN |
3124 |
Hrycyna |
Container of chemical is unlabeled. |
10/22/01 | |
|
BRWN |
3124 Corridor |
Hrycyna |
Corridor obstructed. Remove papers stored on floor. See note 8. |
10 d |
10/26/01 |
|
BRWN |
3124A |
Laskowski |
Chemical containers have labels that are deteriorating and/or unreadable. |
11/2/01 | |
|
BRWN |
3124A |
Laskowski |
Container of chemical is unlabeled. |
11/2/01 | |
|
BRWN |
3124B |
Hrycyna |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/22/01 | |
|
BRWN |
3124B |
Hrycyna |
Eyewash and/or shower is obstructed. See note 8. |
10/22/01 | |
|
BRWN |
3124B |
Hrycyna |
Fire extinguisher obstructed. #2697 See note 8. |
30 d |
10/22/01 |
|
BRWN |
3125 |
Bina |
Stored chemicals are not segregated by hazards (ethyl acetate stored with oxidizers). (CORRECTED at inspection): |
10/1/01 | |
|
BRWN |
3125A |
Bina |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
12/3/01 | |
|
BRWN |
3125B |
Bina |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
12/3/01 | |
|
BRWN |
3129 |
Bina |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
?? | |
|
BRWN |
3130 |
Laskowski |
Corridor obstructed. Remove recycle bin. |
10 d |
10/30/01 |
|
BRWN |
3131A |
Laskowski |
Extension cord used as permanent wiring. Install permanent outlet or use 15-amp maximum fuse/circuit breaker multiple outlet device. |
30 d |
10/30/01 |
|
BRWN |
3134A |
Laskowski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
BRWN |
3134A |
Laskowski |
Container of chemical is unlabeled. LAS will follow up |
11/2/01 | |
|
BRWN |
3134B |
Laskowski |
Chemical containers have labels that are deteriorating and/or unreadable. (brown bottle under fume hood) |
11/2/01 | |
|
BRWN |
3134B |
Laskowski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
BRWN |
3134B |
Laskowski |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
11/2/01 (moved to lower shelf) |
|
BRWN |
3134B |
Laskowski |
Container of chemical is unlabeled. LAS will follow up |
11/2/01 | |
|
BRWN |
3134C |
Laskowski |
Restore aisleway. |
10 d |
11/2/01 |
|
BRWN |
3134C |
Laskowski |
Fire extinguisher obstructed. See note 8. |
30 d |
11/2/01 |
|
BRWN |
3134C |
Laskowski |
Power cord damaged or broken. Electrical tape is unacceptable. (vacuum pump #157) |
10 d |
11/5/01 |
|
BRWN |
3134C |
Laskowski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
BRWN |
3135 |
Hrycyna |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/22/01 | |
|
BRWN |
3135A |
Kenttamaa |
Container of chemical is unlabeled. |
11/19/01 | |
|
BRWN |
3135A |
Kenttamaa |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/19/01 | |
|
BRWN |
3135B |
Kenttamaa |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
11/20/01 | |
|
BRWN |
3135B |
Kenttamaa |
Alcoholic beverages are stored in this area. |
10/20/01 | |
|
BRWN |
3135D |
Bina |
Container of chemical is unlabeled. |
?? | |
|
BRWN |
3144 |
Bina |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
?? |
|
BRWN |
3144 |
Bina |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
?? |
|
BRWN |
3144 |
Bina |
Chemical containers have labels that are deteriorating and/or unreadable. |
?? | |
|
BRWN |
3144 |
Bina |
Container of chemical is unlabeled. |
?? | |
|
BRWN |
3144 |
Bina |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
12/3/01 | |
|
BRWN |
3144A |
Laskowski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
BRWN |
3144A |
Laskowski |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrogen) See note 7. |
11/2/01 | |
|
BRWN |
3144A |
Laskowski |
Container of chemical is unlabeled. LAS will follow up |
11/2/01 | |
|
BRWN |
3144A |
Laskowski |
Power cord damaged or broken. Electrical tape is unacceptable. (Beckman cooler) |
10 d |
11/5/01 |
|
BRWN |
3144A |
Laskowski |
Restore minimum aisle width of 22". (They will turn file cabinet sideways) |
10 d |
11/5/01 |
|
BRWN |
3151 |
Kenttamaa |
Stored chemicals are not segregated by hazards. Nitric and perchloric acids stored with acetic acid and acetic anhydride. (CORRECTED at inspection) [This item has to be an error. No chemicals are kept in 3151] |
10/1/01 | |
|
BRWN |
3151D |
Kenttamaa |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/17/01 |
|
BRWN |
3151F |
Kenttamaa |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/19/01 |
|
BRWN |
3151F |
Kenttamaa |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (argon not capped) See note 7. |
11/2/01 | |
|
BRWN |
3151F |
Kenttamaa |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/19/01 | |
|
BRWN |
3154 |
Hedderich |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrogen) See note 7. |
11/7/01 | |
|
BRWN |
3154 |
Hedderich |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Remove cords from across aisleway. See note 8. |
11/7/01 | |
|
BRWN |
3164 |
Regnier |
Food stored with laboratory equipment and/or chemicals. |
11/20/01 | |
|
BRWN |
3164 |
Regnier |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/20/01 |
|
BRWN |
3164 |
Regnier |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/20/01 |
|
BRWN |
3164 |
Regnier |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
BRWN |
3164 |
Regnier |
Container of chemical is unlabeled. |
11/20/01 | |
|
BRWN |
3164A |
Regnier |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
11/20/01 |
|
BRWN |
3164A |
Regnier |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
BRWN |
3164A |
Regnier |
Container of chemical is unlabeled. |
11/20/01 | |
|
BRWN |
3164A |
Regnier |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (into 3154) |
10 d |
11/20/01 |
|
BRWN |
3165A |
Keyes |
Container of chemical is unlabeled. |
10/30/01 | |
|
BRWN |
3170 |
Regnier |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/20/01 |
|
BRWN |
3170 |
Regnier |
Electrical cord tunnels across aisleways are not acceptable. |
30 d |
12/6/01 |
|
BRWN |
3170 |
Regnier |
Container of chemical is unlabeled. |
11/20/01 | |
|
BRWN |
3170 |
Regnier |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/20/01 |
|
BRWN |
3170 |
Regnier |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid inside flammable storage cabinet. |
11/20/01 | |
|
BRWN |
3170 |
Regnier |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/20/01 | |
|
BRWN |
3170 |
Regnier |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
11/20/01 |
|
BRWN |
3170 |
Regnier |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
11/20/01 |
|
BRWN |
3170 |
Regnier |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
BRWN |
3174B |
Regnier |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (CORRECTED by REM) See note 7. |
10/1/01 | |
|
BRWN |
3175 |
Keyes |
Container of chemical is unlabeled. |
10/29/01 | |
|
BRWN |
3182 |
Regnier |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/20/01 |
|
BRWN |
3182 |
Regnier |
Container of chemical is unlabeled. |
11/20/01 | |
|
BRWN |
3182 |
Regnier |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
BRWN |
3182 |
Regnier |
Fire extinguisher obstructed. (remove clothing) See note 8. |
30 d |
11/20/01 |
|
BRWN |
3184 |
Regnier |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
BRWN |
3184 |
Regnier |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/20/01 |
|
BRWN |
3185 |
Regnier |
Alcoholic beverages are stored in this area. |
11/20/01 | |
|
BRWN |
4102 |
Dirksen |
Workplace not reasonably free of recognized hazards: duplex outlet in kitchenette without GFCI protection. Submit OSHA 113 to REM. REM will issue 18-A. P59 is not required. |
60 d |
12/10/01 |
|
BRWN |
4102 |
Safety -- Susan Greer will handle |
Workplace not reasonably free of recognized hazards. Damaged personal refrigerator in use. |
10 d |
10/30/01 |
|
BRWN |
4103A |
Organic Div -- Susan Greer will handle |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/27/011 |
|
BRWN |
4103E |
Grutzner |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
11/01/01 | |
|
BRWN |
4106 |
Safety |
Workplace not reasonably free of recognized hazards. Chairs are easily tipped over. |
10 d |
11/20/01 |
|
BRWN |
4124 |
Margerum |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
10/8/01 |
|
BRWN |
4125 |
Wilker |
Eyewash and/or shower is obstructed. See note 8. |
10/19/01 | |
|
BRWN |
4125 |
Wilker |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/19/01 |
|
BRWN |
4125A |
Wilker |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/19/01 | |
|
BRWN |
4132 |
Margerum |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/8/01 |
|
BRWN |
4134 |
Margerum |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
error, not a xconnect |
|
|
4134 |
Margerum |
Eyewash and/or shower is obstructed. See note 8. |
10/8/01 | |
|
BRWN |
4134A |
Margerum |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
error, not a xconnect |
|
BRWN |
4134A |
Margerum |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/8/01 | |
|
BRWN |
4135A |
Wilker |
Sign needed to indicate hazard. Tecnecium 99 contaminated fume hoods need to be posted with radioactive stickers. |
30 d |
10/25/01 |
|
BRWN |
4144 |
Raftery |
Open chemical waste containers not in use. |
10/17/01 | |
|
BRWN |
4144A |
Raftery |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. |
30 d |
10/17/01 |
|
BRWN |
4150D |
Raftery |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/17/01 |
|
BRWN |
4151 |
Santini |
Restore aisleway. Remove the extension cord from across the aisle. |
10 d |
10/1/01 |
|
BRWN |
4151D |
Santini |
Minimum clear space of 36 '' not maintained in front of switchboard. |
10 d |
10/1/01 |
|
BRWN |
4152 |
Raftery |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Door blocked. See note 8. |
10/17/01 | |
|
BRWN |
4154 |
Raftery |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. |
30 d |
10/17/01 |
|
BRWN |
4154 |
Raftery |
Restore aisleway. Remove cords from across aisle. |
10 d |
10/17/01 |
|
BRWN |
4154A |
Raftery |
Fire extinguisher obstructed. See note 8. |
30 d |
10/17/01 |
|
BRWN |
4154B |
Raftery |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Door blocked.See note 8. |
10/17/01 | |
|
BRWN |
4164 |
Simpson |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/18/01 | |
|
BRWN |
4164 |
Simpson |
Power cord damaged or broken. Electrical tape is unacceptable. (Coherent dye circulator) |
10 d |
10/18/01 |
|
BRWN |
4165 |
M. Weaver |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrous oxide) See note 7. |
10/3/01 | |
|
BRWN |
4165 |
M. Weaver |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/3/01 |
|
BRWN |
4165 |
M. Weaver |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Remove cord from across aisleway. See note 8. |
11/28/01 | |
|
BRWN |
4165 |
M. Weaver |
Stored chemicals are not segregated by hazards. Hydrogen peroxide and nitric acid stored with flammable materials. (Corrected at inspection) |
10/1/01 | |
|
BRWN |
4165 |
M. Weaver |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/3/01 | |
|
BRWN |
4165 |
M. Weaver |
Restore minimum aisle width of 22". |
10 d |
11/28/01 |
|
BRWN |
4165A |
M. Weaver |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/3/01 | |
|
BRWN |
4165A |
M. Weaver |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/3/01 |
|
BRWN |
4165A |
M. Weaver |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. Emergency exit from 4165A blocked. |
10 d |
11/28/01 |
|
BRWN |
4165A |
M. Weaver |
Open chemical containers not in use. |
10/3/01 | |
|
BRWN |
4165A |
M. Weaver |
Stored chemicals are not segregated by hazards. Hydrogen peroxide stored with combustible materials inside refrigerrator. |
11/28/01 | |
|
BRWN |
4165A |
M. Weaver |
Power cord damaged or broken. Electrical tape is unacceptable. (rheostat on glovebox) |
10 d |
11/22/01 |
|
BRWN |
4165A |
M. Weaver |
Workplace not reasonably free of recognized hazards. Refrigerator was not cold. |
10 d |
11/28/01 |
|
BRWN |
4165A |
M. Weaver |
Container of chemical is unlabeled. Determine identity of unknown in 2L flask and/or dispose of properly if waste. |
11/28/01 | |
|
BRWN |
4165A |
M. Weaver |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/28/01 | |
|
BRWN |
4169 |
M. Weaver |
Open chemical containers not in use. |
11/28/01 | |
|
BRWN |
4169 |
M. Weaver |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/3/01 | |
|
BRWN |
4169 |
M. Weaver |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/3/01 |
|
BRWN |
4169 |
M. Weaver |
Container of chemical is unlabeled. |
11/28/01 | |
|
BRWN |
4169 |
M. Weaver |
Chemical containers have labels that are deteriorating and/or unreadable. |
11/28/01 | |
|
BRWN |
4171B |
M. Weaver |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
12/10/01 | |
|
BRWN |
4171C |
M. Weaver |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
11/10/01 | |
|
BRWN |
4171D |
Szleifer |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
||
|
BRWN |
4174 |
Lytle |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/30/01 threw away hot pot |
|
BRWN |
4174A |
Lytle |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/15/01 |
|
BRWN |
4175 |
M. Weaver |
Power cord damaged or broken. Electrical tape is unacceptable. (fan) |
10 d |
11/28/01 no fan in 4175 or 4175A -- LAS |
|
BRWN |
4175 |
M. Weaver |
Electrical outlet and/or electrical switch is missing coverplate. (central column support) |
11/1/01 | |
|
BRWN |
4175 |
M. Weaver |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/3/01 | |
|
BRWN |
4175 |
M. Weaver |
Restore aisleway. Tubing and cords need to be rerouted from aisleways. |
10 d |
11/20/01 |
|
BRWN |
4175 |
M. Weaver |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Remove cords for aisleway. See note 8. |
11/28/01 | |
|
BRWN |
4175 |
M. Weaver |
Restore minimum aisle width of 22." |
10 d |
11/28/01 |
|
BRWN |
4175A |
M. Weaver |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/3/01 | |
|
BRWN |
4175A |
M. Weaver |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/3/01 |
|
BRWN |
4175A |
M. Weaver |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/30/01 |
|
BRWN |
4175B |
M. Weaver |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
12/10/01 | |
|
BRWN |
4175D |
M. Weaver |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. Remove cardboard boxes from fire escape. |
10 d |
10/3/01 |
|
BRWN |
4184 |
Szleifer |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/15/01 |
|
BRWN |
5124 |
Bower |
Open chemical containers not in use. |
10/19/01 | |
|
BRWN |
5124 |
Bower |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/19/01 |
|
BRWN |
5124 |
Bower |
Eyewash and/or shower is obstructed. (Corrected; trash cans removed from in front of two (2) eyewashes.) See note 8. |
10/2/01 | |
|
BRWN |
5124 |
Bower |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/19/01 | |
|
BRWN |
5125 |
Ramachandran |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
10/29/01 |
|
BRWN |
5125 |
Ramachandran |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/29/01 |
|
BRWN |
5125 |
Ramachandran |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/29/01 |
|
BRWN |
5125 |
Ramachandran |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/29/01 | |
|
BRWN |
5125 |
Ramachandran |
Power cord damaged or broken. Electrical tape is unacceptable. (rheostat and heating pad inside hood B + rheostat and vacuum pump inside hood C + heating pad inside hood D) |
10 d |
10/29/01 |
|
BRWN |
5125 |
Ramachandran |
Open chemical containers not in use. |
10/29/01 | |
|
BRWN |
5125 |
Ramachandran |
Container of chemical is unlabeled. |
10/29/01 | |
|
BRWN |
5125 |
Ramachandran |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/29/01 |
|
BRWN |
5129 |
Ramachandran |
Required exit(s) obstructed. See note 8. |
10/29/01 | |
|
BRWN |
5129 |
Ramachandran |
Fire extinguisher obstructed. See note 8. |
30 d |
10/29/01 |
|
BRWN |
5129 |
Ramachandran |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (2 hydrogen, 2 compressed air, 1 helium) See note 7. |
10/29/01 | |
|
BRWN |
5130A |
Rothwell |
Food stored with laboratory equipment and/or chemicals. |
10/29/01 | |
|
BRWN |
5130A |
Rothwell |
Container of chemical is unlabeled. |
10/29/01 | |
|
BRWN |
5130A |
Rothwell |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/02/01 | |
|
BRWN |
5130B |
Rothwell |
Restore aisleway. Remove telephone cord from across walkway. |
10 d |
10/29/01 |
|
BRWN |
5134 |
Rothwell |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (dimethylamine) See note 7. |
10/29/01 | |
|
BRWN |
5134 |
Rothwell |
Chemical storage refrigerator(s) and/or freezer(s) should be cleaned and/or organized more safely. (round bottom flasks in freezer) |
11/01/01 | |
|
BRWN |
5134 |
Rothwell |
Power cord damaged or broken. Electrical tape is unacceptable. (rheostat + 2 heatring pads) |
10 d |
11/01/01 |
|
BRWN |
5134 |
Rothwell |
Container of chemical is unlabeled. (inside freezer) |
11/02/01 | |
|
BRWN |
5134 |
Rothwell |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/02/01 | |
|
BRWN |
5134A |
Rothwell |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/29/01 |
|
BRWN |
5134A |
Rothwell |
Open chemical containers not in use. |
10/29/01 | |
|
BRWN |
5134A |
Rothwell |
Container of chemical is unlabeled. |
10/29/01 | |
|
BRWN |
5134A |
Rothwell |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/02/01 | |
|
BRWN |
5134B |
Rothwell |
Food stored with laboratory equipment and/or chemicals. |
10/29/01 | |
|
BRWN |
5135 |
Ramachandran |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Eyewash and/or shower is obstructed (2 eyewashes). (CORRECTED at inspection) See note 8. |
10/2/01 | |
|
BRWN |
5135 |
Ramachandran |
Excessive accumulation or abandoned containers of chemical waste. |
10 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Workplace not reasonably free of recognized hazards. (Hood B: Use of chemicals inside fume hood marked for storage only. Hood shash needs to be repaired.) |
10 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Open chemical containers not in use. |
10/29/01 | |
|
BRWN |
5135 |
Ramachandran |
Power cord damaged or broken. Electrical tape is unacceptable. (rheostat, heating pad and dryer inside A + dryer innside hood C + Equatherm stirrer inside hood D) |
10 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Container of chemical is unlabeled. |
10/29/01 | |
|
BRWN |
5135 |
Ramachandran |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/29/01 |
|
BRWN |
5135 |
Ramachandran |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/29/01 | |
|
BRWN |
5144 |
Rothwell |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/29/01 |
|
BRWN |
5150 |
Fenniri |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. See note 8. |
11/2/01 | |
|
BRWN |
5150 |
Fenniri |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/2/01 |
|
BRWN |
5150 |
Fenniri |
Open chemical containers not in use. |
11/2/01 | |
|
BRWN |
5150 |
Fenniri |
Workplace not reasonably free of recognized hazards. Do not store lab coats or other PPE on fume hood where they obstruct or obscure instructions and switches. |
10 d |
11/2/01 |
|
BRWN |
5150 |
Fenniri |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid and other flammablle materials under fume hood B. |
11/2/01 | |
|
BRWN |
5150 |
Fenniri |
Restore aisleway. (southernmost aisle). |
10 d |
11/27/01 |
|
BRWN |
5150 |
Fenniri |
Open chemical waste containers not in use. (Acetone bottle capped by REM) |
11/2/01 | |
| BRWN | 5150A | Fenniri | Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Emergency exit into 5150D is blocked. See note 8. | Immed | 11/27/01 |
|
BRWN |
5150D |
Rothwell |
Workplace not reasonably free of recognized hazards. Do not store lab coats or other PPE on fume hood where they obstruct or obscure instructions and switches. |
10 d |
10/22/01 |
|
BRWN |
5150D |
Rothwell |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/29/01 | |
|
BRWN |
5151A |
Shepson |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
10/18/01 |
|
BRWN |
5151A |
Shepson |
Container of chemical is unlabeled. |
10/18/01 | |
|
BRWN |
5151A |
Shepson |
Electrical cord tunnels across aisleways are not acceptable. |
30 d |
10/18/01 |
|
BRWN |
5151A |
Shepson |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/18/01 | |
|
BRWN |
5164 |
Walton |
PPE required by posted Hazard Assessment Certification not in use. |
10/5/01 | |
|
BRWN |
5164A |
Buriak (note from Buriak group safety person that these cylinders were Prof Walton's) |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. (note from Schmeltzer indicates that these cylinders were Prof Walton's, and are now secure) |
11/5/01 | |
|
BRWN |
5164A |
Buriak |
Open chemical containers not in use. |
11/5/01 | |
|
BRWN |
5164A |
Buriak |
Alcoholic beverages are stored in this area. |
11/5/01 | |
|
BRWN |
5165 |
Grant |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/9/01 |
|
BRWN |
5165 |
Grant |
Restore minimum aisle width of 22". |
10 d |
11/9/01 |
|
BRWN |
5165 |
Grant |
Container of chemical is unlabeled. |
11/9/01 | |
|
BRWN |
5165 |
Grant |
Open chemical containers not in use. |
11/9/01 | |
|
BRWN |
5165C |
Shepson |
Eyewash and/or shower is obstructed. See note 8. |
10/18/01 | |
|
BRWN |
5165C |
Shepson |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
10/18/01 | |
|
BRWN |
5165C |
Shepson |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid under the fume hood. |
10/18/01 | |
|
BRWN |
5168 |
Walton |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/23/01 |
|
BRWN |
5168 |
Walton |
Food stored with laboratory equipment and/or chemicals. |
10/29/01 | |
|
BRWN |
5168 |
Walton |
Power cord damaged or broken. Electrical tape is unacceptable. (cord cut by REM) |
10 d |
10/2/01 |
|
BRWN |
5172 |
Buriak |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/5/01 |
|
BRWN |
5174 |
Buriak |
Chemical containers have labels that are deteriorating and/or unreadable. |
11/5/01 | |
|
BRWN |
5174A |
Buriak |
Air purifying respirators ("gas masks") are not permitted in laboratories unless lab staff are a part of the Purdue Respiratory Protection Program. A gas mask was removed. (corrected at inspection) (predates Buriak group significantly) |
10/2/01 | |
|
BRWN |
5174A |
Buriak |
Container of chemical is unlabeled. |
11/5/01 | |
|
BRWN |
5175 |
Grant |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/9/01 |
|
BRWN |
5186 Corridor |
Fenniri |
Corridor obstructed. Remove filing cabinets from the corridor. See note 8. |
10 d |
12/10/01 |
|
WTHR |
055A |
Kenttmaa |
Excess flammables stored outside of approved cabinet and/or safety cans. |
60 d |
11/19/01 |
|
WTHR |
063 |
Cooks |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrogen) (CORRECTED at inspection) See note 7. |
10/9/01 | |
|
WTHR |
070 - 086 Corridor |
Dirksen |
Corridor obstructed. Remove items stored in the corridor. See note 8. |
10 d |
12/6/01 |
|
WTHR |
073 |
Santini |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
10/26/01 |
|
WTHR |
073 |
Santini |
Ensure compressed air regulator nozzles for cleaning are limited to 30 PSI. |
60 d |
11/16/01 |
|
WTHR |
075 |
Santini |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
10/30/01 |
|
WTHR |
075 |
Santini |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. See note 8. |
10/10/01 | |
|
WTHR |
075 |
Santini |
Ensure compressed air regulator nozzles for cleaning are limited to 30 PSI. |
60 d |
11/15/01 |
|
WTHR |
121 |
Smith |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/31/01 | |
|
WTHR |
121 |
Smith |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/15/01 |
|
WTHR |
121 |
Smith |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (helium) See note 7. |
10/25/01 | |
|
WTHR |
121 |
Smith |
Container of chemical is unlabeled. |
10/22/01 | |
|
WTHR |
121 |
Smith |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/31/01 |
|
WTHR |
121 |
Smith |
Power cord damaged or broken. Electrical tape is unacceptable. (hotplate/stirrer + Variac rheostat) |
10 d |
10/18/01 |
|
WTHR |
121 |
Smith |
Chemical containers have labels that are deteriorating and/or unreadable. (below fume hood B). Example note 4. |
10/16/01 | |
|
WTHR |
121 |
Smith |
Air purifying respirators ("gas masks") are not permitted in laboratories unless lab staff are a part of the Purdue Respiratory Protection Program. A gas mask was removed. (CORRECTED by REM at inspection) |
(10/1/01) | |
|
WTHR |
140A |
Dirksen |
Ensure compressed air regulator nozzles for cleaning are limited to 30 PSI. |
60 d |
11/16/01 |
|
WTHR |
148 |
Lipschutz |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
12/5/01 | |
|
WTHR |
148 |
Lipschutz |
Eyewash and/or shower is obstructed. See note 8. |
10/23/01LAS | |
|
WTHR |
148 |
Lipschutz |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/19/01 |
|
WTHR |
149 |
Lipschutz |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/19/01 |
|
WTHR |
149 |
Lipschutz |
Failure to post written Hazard Assessment Certification. See note 11. |
5 d |
12/5/01 verified, been there since? |
|
WTHR |
149 |
Lipschutz |
Eyewash and/or shower is obstructed. See note 8. |
10/23/01LAS | |
|
WTHR |
149 |
Lipschutz |
Open chemical containers not in use (acid bath). (CORRECTED at inspection) |
10/8/01 | |
|
WTHR |
149 |
Lipschutz |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
12/5/01 | |
|
WTHR |
149A |
Lipschutz |
Remove orphaned blood bags from freezer and dispose of properly. |
10 d |
11/29/01 |
|
WTHR |
165 |
Bower |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/26/01 |
|
WTHR |
168 |
Bower |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/26/01 |
|
WTHR |
301 Corridor |
Library |
Corridor obstructed. Remove can and bookcase. See note 8. |
10 d |
12/7/01 |
|
WTHR |
301A |
Library |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
12/7/01 | |
|
WTHR |
310B |
Library |
Restore aisleway. Remove cord from aisleway. |
10 d |
12/7/01 |
|
WTHR |
316 |
Biology (emailed Mason and Browning 10/26) |
Container of chemical is unlabeled. (identify liquids in specimen containers) |
10/5/01 | |
|
WTHR |
316 |
Biology (emailed Mason and Browning 10/26) |
Extension cord used as permanent wiring. Install permanent outlet or use 15-amp maximum fuse/circuit breaker multiple outlet device. (CORRECTED aty inspection) |
30 d |
10/5/01 |
|
WTHR |
316 |
Biology (emailed Mason and Browning 10/26) |
Workplace not reasonably free of recognized hazards. Remove table from in front of heat register. |
10 d |
10/15/01 |
|
WTHR |
317 |
Biology (emailed Mason and Browning 10/26) |
Food stored with laboratory equipment and/or chemicals. |
10/5/01 | |
|
WTHR |
317 |
Biology (emailed Mason and Browning 10/26) |
Workplace not reasonably free of recognized hazards. Remove refrigerator from in front of heat register. |
10 d |
10/15/01 |
|
WTHR |
317B |
Biology (emailed Mason and Browning 10/26) |
Chemical containers have labels that are deteriorating and/or unreadable. |
10/5/01 | |
|
WTHR |
322 |
Low |
Waste containers are improperly labeled. All hazardous waste containers must have the words 'HAZARDOUS WASTE' clearly visible on them. |
10/30/01 | |
|
WTHR |
322 |
Low |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (CORRECTED at inspection) |
10 d |
(10/5/01) |
|
WTHR |
322 |
Low |
Open chemical containers not in use. |
10/30/01 | |
|
WTHR |
322 |
Low |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/30/01 | |
|
WTHR |
322 |
Low |
Container of chemical is unlabeled. |
10/30/01 | |
|
WTHR |
327 |
Low |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/30/01 |
|
WTHR |
327 |
Low |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/30/01 | |
|
WTHR |
327 |
Low |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
10/30/01 | |
|
WTHR |
327 |
Low |
Container of chemical is unlabeled. |
10/30/01 | |
|
WTHR |
327 |
Low |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/30/01 |
|
WTHR |
327 |
Low |
Peroxidizable chemicals not dated or stored past expiration date. (ether inside fume hood B) |
10/30/01 | |
|
WTHR |
331A |
Biochem Div (Empty Faculty Office) |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (door to 333A) |
10 d |
10/30/01(on Low report) |
|
WTHR |
333A |
Biochem Div (unassigned Lab) |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (door to 333B) |
10 d |
10/30/01(on Low report) |
|
WTHR |
333B |
Low |
Open chemical waste containers not in use. |
10/30/01 | |
|
WTHR |
333B |
Low |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/30/01 |
|
WTHR |
333B |
Low |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/30/01 | |
|
WTHR |
333B |
Low |
Waste containers are improperly labeled. All hazardous waste containers must have the words 'HAZARDOUS WASTE' clearly visible on them. |
10/30/01 | |
|
WTHR |
333B |
Low |
Excessive accumulation or abandoned containers of chemical waste. |
10 d |
10/30/01 |
|
WTHR |
333B |
Low |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
10/30/01 |
|
WTHR |
333B |
Low |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/30/01 |
|
WTHR |
333B |
Low |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (door to 333C) |
10 d |
10/30/01 |
|
WTHR |
333B |
Low |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
10/30/01 | |
|
WTHR |
333C |
Biochem div (unassigned lab) |
Obstructions, including storage, shall not be placed in the required width of a means of egress, except projections as allowed by the Building Code. Means of egress shall not be obstructed in any manner. (door to 333B) |
10 d |
12/5/01 |
|
WTHR |
345B |
Biochem div shared space |
Open chemical waste containers not in use. |
12/5/01 | |
|
WTHR |
345C |
Biochem div shared shared space |
Container of chemical is unlabeled. Two (2) Steelsack trash bags with unknown chemicals inside. |
12/5/01 they are old (18" dia) computer disks | |
|
WTHR |
352 |
VanEtten |
Excessive accumulation or abandoned containers of chemical waste. |
10 d |
12/5/01 |
|
WTHR |
352 |
VanEtten |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
10/10/01 error, there are stickers |
|
WTHR |
352 - 359 |
VanEtten |
Corridor obstructed. Remove the file cabinets from the corridor. See note 8. |
10 d |
11/1/01 This "internal corridor + storage" per SMAS |
|
WTHR |
353 |
VanEtten |
Power cord damaged or broken. Electrical tape is unacceptable. (vacuum pump) |
10 d |
12/6/01 Chem Shop work order |
|
WTHR |
354 |
VanEtten |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
12/5/01 | |
|
WTHR |
354 |
VanEtten |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
WTHR |
354 |
VanEtten |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/20/01 |
|
WTHR |
354 |
VanEtten |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
WTHR |
357 |
Low |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/30/01 |
|
WTHR |
357 |
Low |
Move containers of liquids stored above eye level to eye level or below. |
30 d |
10/30/01 |
|
WTHR |
357 |
Low |
Container of chemical is unlabeled. |
10/30/01 | |
|
WTHR |
357 |
Low |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/30/01 |
|
WTHR |
357 |
Low |
Eyewash and/or shower is obstructed. See note 8. |
10/30/01 | |
|
WTHR |
357 |
Low |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/30/01 |
|
WTHR |
358 |
VanEtten |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/20/01 | |
|
WTHR |
358 |
VanEtten |
No employee shall be allowed to consume food or beverages in a toilet room nor in any area exposed to a toxic material. (Frito's corn chips bag in bio-trash) |
11/20/01 | |
|
WTHR |
358 |
VanEtten |
Power cord damaged or broken. Electrical tape is unacceptable. (Vortex mixer) |
10 d |
11/20/01 |
|
WTHR |
358 |
VanEtten |
Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. Remove bio-waste box from in front of door. See note 8. |
11/20/01 | |
|
WTHR |
358 |
VanEtten |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
12/5/01 | |
|
WTHR |
358 |
VanEtten |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. (CORRECTED at inspection, moved from inside of door to outside) |
10 d |
10/5/01 |
|
WTHR |
358 |
VanEtten |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/20/01 |
|
WTHR |
365 |
Hallenga |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/18/01 |
|
WTHR |
369 |
Hallenga |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/18/01 | |
|
WTHR |
373 |
Lipton |
Clean broken glass or plastic sharps should be collected in a cardboard box or other strong, secure disposable container. Needles, razor blades, scalpels, etc., must be disposed of in puncture proof plastic containers. |
11/2/01 | |
|
WTHR |
373 |
Lipton |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
WTHR |
373 |
Lipton |
Container of chemical is unlabeled. |
11/2/01 | |
|
WTHR |
373 |
Lipton |
Power cord damaged or broken. Electrical tape is unacceptable. (fume hood D) |
10 d |
11/2/01 |
|
WTHR |
373A |
Lipton |
Power cord damaged or broken. Electrical tape is unacceptable. (regulator inside hood) |
10 d |
11/2/01 |
|
WTHR |
377 |
Lipton |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
11/2/01 (this was an inspection error) |
|
WTHR |
377 |
Lipton |
Container of chemical is unlabeled. |
11/2/01 | |
|
WTHR |
377 |
Lipton |
Power cord damaged or broken. Electrical tape is unacceptable. (two (2) stirrers inside fume hood B) |
10 d |
11/2/01 |
|
WTHR |
377 |
Lipton |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
WTHR |
377 |
Lipton |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/2/01 |
|
WTHR |
377B |
Lipton |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. (nitrogen) See note 7. |
11/2/01 | |
|
WTHR |
402 |
Chmielewski |
Restore aisleway. Remove projector cord from aisleway. |
10 d |
10/18/01 |
|
WTHR |
405 |
Chmielewski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/18/01 | |
|
WTHR |
405 |
Chmielewski |
Container of chemical is unlabeled. |
10/18/01 | |
|
WTHR |
405 |
Chmielewski |
Power cord damaged or broken. Electrical tape is unacceptable. (tube stirrer inside fume hood C + Variac rheostat inside fume hood G) |
10 d |
10/18/01 |
|
WTHR |
410 |
Wei |
Workplace not reasonably free of recognized hazards: duplex outlet in kitchenette without GFCI protection. Submit OSHA 113 to REM. REM will issue 18-A. P59 is not required. |
60 d |
11/7/01 LAS submitted 113 |
|
WTHR |
410A |
Wei |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
11/8/01 |
|
WTHR |
413 |
Wei |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/24/01 | |
|
WTHR |
413 |
Wei |
Open chemical waste containers not in use. |
10/24/01 | |
|
WTHR |
413 |
Wei |
Power cord damaged or broken. Electrical tape is unacceptable. (vacuum pump under fume hood C + aerator inside fume hood C + Variac rheostat inside hood F) |
10 d |
11/7 variac & aerator, 11/27 pump |
|
WTHR |
413 |
Wei |
Workplace not reasonably free of recognized hazards: duplex outlet in kitchenette without GFCI protection. Submit OSHA 113 to REM. REM will issue 18-A. P59 is not required. |
60 d |
11/7/01 LAS submitted 113 |
|
WTHR |
413 |
Wei |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
11/5/01 |
|
WTHR |
415 |
Thompson |
Power cord damaged or broken. Electrical tape is unacceptable. (Milletorr inside fume hood E) |
10 d |
11/5/01 |
|
WTHR |
415 |
Thompson |
Electrical equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. (dryers inside sink basins) |
11/5/01 | |
|
WTHR |
415 |
Thompson |
Chemical hood, glovebox, and/or laminar flow filtered air unit unsafe due to excessive accumulation of containers and other materials. (fume hood B) |
10 d |
11/5/01 |
|
WTHR |
415 |
Thompson |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/5/01 |
|
WTHR |
415 |
Thompson |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/5/01 | |
|
WTHR |
417 |
Thompson |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
11/5/01 |
|
WTHR |
417 |
Thompson |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/5/01 | |
|
WTHR |
417 |
Thompson |
Power cord damaged or broken. Electrical tape is unacceptable. (incubator under fume hood) |
10 d |
11/3/01 |
|
WTHR |
419 |
Lipton |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/2/01 | |
|
WTHR |
419 |
Lipton |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/2/01 | |
|
WTHR |
419 |
Lipton |
Chemical spills on the floor and/or working surfaces must be cleaned. [aluminum chloride (anhydrous) inside inorganic chemical storage cabinet] |
10 d |
11/2/01 |
|
WTHR |
419 |
Lipton |
Chemical storage refrigerator(s) and/or freezer(s) should be cleaned and/or organized more safely. (dairy bin) |
11/2/01 | |
|
WTHR |
419A |
Lipton |
Alcoholic beverages are stored in this area. |
11/2/01 | |
|
WTHR |
423A |
Thompson/Chmielewski |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/5/01 (Thompson group fix) |
|
|
WTHR |
423A |
Thompson/Chmielewski |
Power cord damaged or broken. Electrical tape is unacceptable. (immersion cooler inside fume hood E + vacuum pump under fume hood F) |
10 d |
11/3/01 (Thompson group fix) |
|
WTHR |
428 Corridor |
Org Div (Grutzner will handle via D. Jordan) |
Corridor obstructed. Remove table from corridor. See note 8. |
10 d |
11/9/01 |
|
WTHR |
430 |
Morrison |
No employee shall be allowed to consume food or beverages in a toilet room nor in any area exposed to a toxic material. |
10/18/01 (unnecessary desig sticker removed) | |
|
WTHR |
430C |
Morrison |
Excessive fire fuel loading (paper and/or other combustibles). |
10/18/01 | |
|
WTHR |
430C |
Morrison |
Container of chemical is unlabeled. |
10/18/01 | |
|
WTHR |
430D |
Morrison |
Container of chemical is unlabeled. |
10/18/01 | |
|
WTHR |
440 |
Morrison |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/29/01 | |
|
WTHR |
440 |
Morrison |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
10/29/01 | |
|
WTHR |
440 |
Morrison |
Air purifying respirators ("gas masks") are not permitted in laboratories unless lab staff are a part of the Purdue Respiratory Protection Program. A gas mask was removed. (CORRECTED by REM at inspection) |
10/9/01 | |
|
WTHR |
440 |
Morrison |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/29/01 |
|
WTHR |
440 |
Morrison |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/29/01 |
|
WTHR |
440 |
Morrison |
Container of chemical is unlabeled. |
10/29/01 | |
|
WTHR |
440B |
Morrison |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
10/18/01 |
|
WTHR |
440B |
Morrison |
No employee shall be allowed to consume food or beverages in a toilet room nor in any area exposed to a toxic material. |
10/18/01 | |
|
WTHR |
440B |
Morrison |
Possible potable water supply cross connection exists. Hose(s) from spigot placed inside drain and/or touch bottom of basin. Cut hose(s) to a length no more than halfway below flood plane. see note 1. |
30 d |
10/18/01 |
|
WTHR |
440B |
Morrison |
Workplace not reasonably free of recognized hazards. Do not store lab coats or other PPE on fume hood where they obstruct or obscure instructions and switches. |
10 d |
10/18/01 |
|
WTHR |
440B |
Morrison |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/18/01 | |
|
WTHR |
440B |
Morrison |
Container of chemical is unlabeled. |
10/29/01 | |
|
WTHR |
441 |
Grutzner |
Eyewash and/or shower is obstructed. See note 8. |
11/01/01 | |
|
WTHR |
441 |
Grutzner |
Food stored with laboratory equipment and/or chemicals. |
11/01/01 | |
|
WTHR |
442 |
Fuchs |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/20/01 | |
|
WTHR |
442 |
Fuchs |
Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See note 6. |
10 d |
Correct stickers have been on hoods here for years |
|
WTHR |
442 |
Fuchs |
Food stored with laboratory equipment and/or chemicals. |
10/25/01 | |
|
WTHR |
442 |
Fuchs |
Open chemical waste containers not in use. |
10/25/01 | |
|
WTHR |
442 |
Fuchs |
Container of chemical is unlabeled. |
10/25/01 | |
|
WTHR |
444 Corridor |
Fuchs |
Corridor obstructed. Remove bookshelves and cabinets from corridor. See note 8. |
10 d |
12/3/01 |
|
WTHR |
450 Corridor |
Fuchs |
Corridor obstructed. Remove bookcase, trash can and file cabinets. See note 8. |
10 d |
This is not corridor. |
|
WTHR |
450A |
Fuchs |
Container of chemical is unlabeled. |
10/25/01 | |
|
WTHR |
450A |
Fuchs |
Alcoholic beverages are stored in this area. |
11/16/01 | |
|
WTHR |
450A |
Fuchs |
Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below. See note 3. |
30 d |
11/16/01 |
|
WTHR |
450A |
Fuchs |
Power cord damaged or broken. Electrical tape is unacceptable. (fume hoods C + D + F) |
10 d |
10/22/01 |
|
WTHR |
450A |
Fuchs |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
10/18/01 | |
|
WTHR |
450E |
Fuchs |
Open chemical waste containers not in use. |
10/25/01 | |
|
WTHR |
450E |
Fuchs |
Power cord damaged or broken. Electrical tape is unacceptable. (Thermolyne heater/stirrer inside fume hood J) |
10 d |
10/18/01 |
|
WTHR |
450E |
Fuchs |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
10/20/01 | |
|
WTHR |
450E |
Fuchs |
Heat resistant pad (ceramic tile or metal stove and counter top pad) needed under coffee maker(s) and/or hot water heater(s). |
60 d |
10/25/01 |
|
WTHR |
450E |
Fuchs |
Excessive use of floor space for containers of chemicals, equipment, and/or other items restrict aisleways. |
10/25/01 | |
|
WTHR |
450E |
Fuchs |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
10/25/01 |
|
WTHR |
454 |
Negishi |
Stored chemicals are not segregated by hazards. Nitric acid stored with acetic acid. (CORRECTED at inspection) |
10/8/01 | |
|
WTHR |
454 |
Negishi |
Move containers of liquids stored above eye level to eye level or below. |
30 d |
11/19/01 |
|
WTHR |
454 |
Negishi |
Container of chemical is unlabeled. |
11/19/01 | |
|
WTHR |
454 |
Negishi |
Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See note 5. |
10 d |
11/19/01 |
|
WTHR |
454 |
Negishi |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/19/01 | |
|
WTHR |
454 |
Negishi |
Power cord damaged or broken. Electrical tape is unacceptable. (vacuum pump cord on cart by fume hood A) |
10 d |
11/19/01 |
|
WTHR |
463 |
Grutzner |
Container of chemical is unlabeled. |
11/01/01 | |
|
WTHR |
463 |
Grutzner |
Restore aisleway. |
10 d |
11/01/01 |
|
WTHR |
463 |
Grutzner |
Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See note 2. and see Acronyms.xls |
11/01/01 | |
|
WTHR |
463 |
Grutzner |
Food stored with laboratory equipment and/or chemicals. |
11/01/01 | |
|
WTHR |
465 |
Negishi |
Open chemical containers not in use. |
11/19/01 | |
|
WTHR |
465 |
Negishi |
PPE required by posted Hazard Assessment Certification not in use. See note 11. |
11/19/01 | |
|
WTHR |
465 |
Negishi |
Unsecured or inadequately secured compressed gas cylinder(s). Uncapped cylinders without regulators are unacceptable. Cylinders with regulators should be secured individually. See note 7. |
11/19/01 | |
|
WTHR |
465 |
Negishi |
Container of chemical is unlabeled. |
11/19/01 | |
|
WTHR |
465 |
Negishi |
Power cord damaged or broken. Electrical tape is unacceptable. (rheostat inside fume hood A + equipment inside fume hood C + rheostat inside fume hood F) |
10 d |
11/19/01 |
|
WTHR |
465B |
Negishi |
Excessive fire fuel loading (paper and/or other combustibles). Storage is unstable as well as a fire hazard. |
12/10/01 | |
|
WTHR |
475 |
Chmielewski |
Power cord damaged or broken. Electrical tape is unacceptable. (tube spinner inside fume hood D + Variac rheostat inside fume hood E + refrigerator with PUID #836400) |
10 d |
10/30/01 |
|
WTHR |
475 |
Chmielewski |
Fire extinguisher obstructed. See note 8. |
30 d |
10/18/01 |
|
WTHR |
475 |
Chmielewski |
Container of chemical is unlabeled. |
10/18/01 | |
|
WTHR |
475 |
Chmielewski |
Open chemical containers not in use. |
10/18/01 | |
|
WTHR |
475A |
Chmielewski |
Container of chemical is unlabeled. |
10/18/01 | |
|
WTHR |
481 Corridor |
Chmielewski |
Corridor obstructed. Remove trash bucket from corridor. [(custodian supervisor alerted that this might be a bldg services issue -- i.e.group says custodian puts the basket in the hallway.)] |
10 d |
10/18/01 |
Note on meanings of recommended abatement period and indemnification requirements:
Interpret "Immediate" to mean do it as soon as is humanly
possible. Then notify as per instructions above with date and
signature beside each item corrected. Note that Chemistry will not be re-indemnified
until we have
(a) fixed all the 30d and less-than-30d items, and
(b) formally committed to the longer term ones.
What we do right.... is not noted on the inspection form. Too damn bad, but it's just a whole lot more than we pay enough people to do. They (REM people, everybody) know we do more stuff right than wrong. They remark on it during inspections when a chance arises and they think of it. But the inspections are not about congratulating your lab for the things it does right. They are for focusing on the deficiencies. Don't let that give you the impression that the deficiencies predominate; they don't.
Physical Facilities items: These below will be taken care of by Physical Facilities (Sign Shop and other sections of Facilities Services, Fire Safety & Equipment Services....) and REM will be notified by those sections; no action is required from other staff. However, if you happen to notice that something here has still not been corrected after some length of time, please feel free to do us the favor of mentioning it in an email to me.
|
BRWN |
B103 |
Fire extinguisher inspection tag not current. #0210 |
30 d |
||
|
BRWN |
B125A |
Workplace not reasonably free of recognized hazards. Replace room number sign on this door. (The sign somehow got posted on the back of the entrance door to B125). |
10 d |
LAS will verify and sign | |
|
BRWN |
1135B |
Restore room fire resistivity - patch large space around small diameter pipe through floor. |
30 d |
||
|
BRWN |
1135B |
Water dripping onto floor from somewhere high above at west side (closer to front). |
variable |
||
|
BRWN |
1152A |
As per Thedans and posted notice removal is scheduled for this semester |
Spray-on insulation on ceiling must be labeled as to asbestos content. |
30 d |
|
|
BRWN |
1154 |
Electrical box (wires have been removed) on east wall, toward south) needs cover plate. |
60 d |
||
|
BRWN |
1199A |
Exit light is out. (One bulb is burned out or missing.) |
|||
|
BRWN |
1199A |
Door sill screws are loose, trip hazard, at east building exit, southmost door. Re-tape foyer carpet. |
10 d |
||
|
BRWN |
2180 |
Noisy motor in mechanical room. |
FYI | ||
|
BRWN |
3124 |
Fire extinguisher not mounted. #0607 |
30 d |
10/22/01(Hrycyna report) | |
|
BRWN |
3124B |
Fire extinguisher not mounted. #0370 |
30 d |
||
|
BRWN |
3135C |
Workplace not reasonably free of recognized hazards. Door lock is difficult to open. |
10 d |
||
|
BRWN |
3151F |
Fire extinguisher inspection tag not current. #2198 |
30 d |
||
|
BRWN |
3154 |
Workplace not reasonably free of recognized hazards. Repair and restore water pressure to the eyewash./shower. |
10 d |
||
|
BRWN |
4164 |
Fire extinguisher not mounted. #2645 |
30 d |
||
|
BRWN |
4174 |
Fire extinguisher not mounted. #2417 |
30 d |
||
|
BRWN |
4174A |
Light in emergency fire escape out. |
|||
|
BRWN |
4175D |
Restore room fire resistivity - patch holes through walls or floor. |
30 d |
||
|
BRWN |
5125 -5135 Corridor |
Electrical outlet and/or electrical switch is missing coverplate. |
|||
|
BRWN |
5125C |
Restore housekeeping. (5 gallon bucket with used glassware) |
10 d |
||
|
BRWN |
5125C |
Workplace not reasonably free of recognized hazards. (replace light bulb) |
10 d |
||
|
BRWN |
5130A |
Workplace not reasonably free of recognized hazards. Door will not lock. Repair latch. |
10 d |
||
|
WTHR |
073 Corridor |
Exit light is out. |
|||
|
WTHR |
075 Corridor |
Exit light is out. |
|||
|
WTHR |
402 |
Return exit sign to proper upright position. |
|||
|
WTHR |
428 |
Fire extinguisher inspection tag not current. #7179 |
30 d |