Report supervisor-room number mistakes to Linda Swihart

As of 03/22/2005 12:54 PM only the white ones remain

Super

room

item

itemtext

recomm abatement time

abated

reply expected from:

??

5th Floor

labels

Container of chemical is unlabeled. Bucket of unknown sludge sitting on large duct WSW across walking path from 516 space.

immed

6-14-04

Swihart

Biochem Div

345E

width

Restore minimum aisle width of 22".

10 days

7-30-04

biochem div head

Biochem Div

345E

egress

Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. (Door to 345F is blocked.)

immed

7-19-04

biochem div head

Biochem Div

352 Corridor

corridor

Corridor obstructed. Remove equipment, furniture or other items stored in the corridor.

10 days

7-1-04

biochem div head

Biochem Div    Chmielewski

354

postdoor

Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See http://www.purdue.edu/rem/home/forms/DOORPOST.DOC

10 days

7-1-04

biochem div head

Biochem Div Chmielewski

354

hazass

Failure to post written Hazard Assessment Certification. See http://www.purdue.edu/rem/home/forms/HazAsTmp.doc and follow instructions/directions.

5 days

7-1-04

biochem div head

Biochem Div  Chmielewski

354

fraycord

Power cord damaged or broken. Electrical tape is unacceptable. (Fisher Oven)

10 days

  7-1-04                  note: no oven found

biochem div head

Cooks

062

machineguard

Machine guard is missing. The 13" drill press is without a chuck guard.

immed

5-20-04

Chen

Cooks

062

electricspace

Minimum clear space of 36 '' not maintained in front of switchboard. In SSE corner of room, 4 switch boxes are not reachable.

10 days

5-13-04

Chen

Creative Arts

182, in corridor

firedoor2

Fire doors must not be left propped open unless on magnetic hold opens that close when the fire alarm sounds.

immed

6-14-04

Swihart

Dirksen

015

sprinklers

Interference to sprinkler discharge because of building contents. Minimum vertical clearance between sprinklers and material below shall be 18". Stored lamps/light panels too close to sprinklers.

immed

6-4-04

Darrel

Dirksen

016D

corddamage

Flexible cords and/or cables not protected from accidental damage. Extension cord extends through doorway.

immed

6-4-04

Darrel

Dirksen

027, in corridor

firedoor2

Corridor fire doors must not be left propped open, without magnetic hold open devices that close if fire alarm sounds.

immed

6-4-04

Darrel

Dirksen

040

machineguard

Machine guard is missing. Delta table saw is without a blade guard.

immed

5-26-04

Darrel

Dirksen

040B

fraycord

Power cord damaged or broken. Electrical tape is unacceptable. The paint shaker's in-line on/off switch is broken, exposing wires.

10 days

6-7-04

Darrel

Dirksen

513

wastedisp

Apparently abandoned chemical waste -- used silica.

10 days

4-15-04 Darrel

Dirksen

581

sprinklers

Interference to sprinkler discharge. Minimum vertical clearance between sprinklers and material below is 18". Sprinklers obstructed in several locations, fixed one, could not reach others.

immed

4-16-04

Darrel

Dirksen

B180

aisle

Restore aisleway near elevator.

10 days

6-4-04 Darrel

Dirksen?

162B

aisle

Restore aisleway. There is storage in the aisle in this mechanical room.

10 days

5-18-04

Darrel

Dirksen?

506

fuelload

Excessive or unsafe fire fuel load/storage. Excessive plastics and paper, wood, some leaning on hot radiators.

immed

6-18-04

Darrel

Fuchs

450A

genduty

Workplace not reasonably free of recognized hazards. Need SOP for Ozonolysis set-up. Not covered in the Chemical Hygiene Plan manual.

10 days

      6-28-04 Ozonolysis Procedures Manual is in 4103 from Doug Lantrip

Lee

Grutzner

441

fraycord

Power cords damaged or broken. There appears to be a nontrivial collection of small appliances set aside in need of cord repairs, but it also appears that they are just collecting dust. Send for repairs or dispose ASAP.

10 days

Aug 1 .04

Grutzner

Grutzner

463

fraycord

Power cords damaged or broken. Corning hotplate stirrer in hood C, also Variac in hood B.

10 days

Aug 1 .04

Grutzner

Kais/Szleifer

265

gfci

Workplace not reasonably free of recognized hazards: duplex outlet in kitchenette without GFCI protection. Submit OSHA 113 to REM. REM will issue 18-A. P59 is not required. (3 NEEDED)

60 days

8-2-04

Swihart

Kitchenette

202

gfci

Workplace not reasonably free of recognized hazards: duplex outlet in kitchenette without GFCI protection. Submit OSHA 113 to REM. REM will issue 18-A. P59 is not required.

60 days

8-2-04

Swihart

Lipschutz

145 to 150,in corridor

corridor

Corridor obstructed. Remove equipment, furniture or other items stored in the corridor: credenza, desk and two book cases.

10 days

6-7-04

Lipschutz or Swihart

Lipschutz

155 to 159, in corridor

corridor

Corridor obstructed. Remove equipment, furniture or other items stored in the corridor: 5 bookcases.

10 days

7-5-04

Lipschutz or Swihart

Low

327D

hazass

Failure to post written Hazard Assessment Certification. See http://www.purdue.edu/rem/home/forms/HazAsTmp.doc and follow instructions/directions.

5 days

6-19-04

Simon

Low

327E

hazass

Failure to post written Hazard Assessment Certification. See http://www.purdue.edu/rem/home/forms/HazAsTmp.doc and follow instructions/directions.

5 days

6-19-04

Simon

Low

333B

opencont

Open chemical containers not in use.

immed

at inspection Simon

Low

333C

washaccess

Eyewash and/or shower is obstructed.

immed

5-20-04

Simon

Low

333C

combuststorage

Combustible materials not stored safely. Flammables stored next to ignition source inside fume hood.

immed

at inspection

Simon

Low

333C

labels

Container of chemical is unlabeled.

immed

at inspection Simon

Low

357

desig

Failure to designate areas for select carcinogens, reproductive hazards, and/or extremely toxic chemicals. Use supplied "CAUTION" stickers as needed in these areas. See http://www.purdue.edu/rem/home/booklets/crdalist.doc

10 days

6-4-04

Simon

Low

357

opencont

Open chemical containers not in use.

immed

at inspection Simon

Low

357

combuststorage

Combustible materials not stored safely. Methyl alcohol stored next to hot plate/stirrer inside fume hood.

immed

at inspection

Simon

Low

357

labels

Container of chemical is unlabeled.

immed

at inspection Simon

Low

357

genduty

Workplace not reasonably free of recognized hazards. Do not hang lab coats on cylinder valves.

10 days

at inspection

Simon

Low

357

refrig

Chemical storage refrigerator(s) and/or freezer(s) neither lab safe nor posted as "NO FLAMMABLES." See http://www.purdue.edu/rem/home/forms/flamesaf.doc

10 days

6-4-04

Simon

Morrison

430C

firedoor2

Fire doors must not be left propped open when room is unattended. Doors are posted KEEP CLOSED AT ALL TIMES .

immed

6-10-04

Ho

Morrison

430C

segregate

Stored chemicals are not segregated by hazards. Concentrated strong oxidizing acids (nitric, sulfuric… under hood B) are not compatible with much else, need separate storage.)

immed

6-11-04

Ho

Morrison/Wei

440B

firedoor2

Fire doors must not be left propped open when room is unattended. Doors are posted KEEP CLOSED AT ALL TIMES.

immed

6-10-04

Ho

Morrison/Wei

440B

cylinder

Unsecured or inadequately secured compressed gas cylinder(s). Uncapped should be secured individually.

immed

6-10-04

Ho

Morrison/Wei

440B

flamcab

Excess flammables stored outside of approved cabinet and/or safety cans.

60 days

6-11-04

Ho

Morrison/Wei

440B

labels

Containers of chemicals unlabeled. Hood D. Untended research chemical containers must have ID.

immed

6-10-04

Ho

Morrison/Wei

440B

openwaste

Open chemical waste containers not in use. Hood D, RBF with funnel identified as waste by other lab staff.

immed

6-10-04

Ho

Pirolo

427

misc

Need visible emergency evacuation alarm and/or more audible alarm installed in immediate area (Glassblower Laboratory). Department submit P-59 for estimate to repair. Department expense to repair.

60 days

*****

Robinson or Dirksen

Raftery

4144A

hazasstailor

Hazard assessment certification is posted but is not tailored to this work area. Re-create without unnecessary items, new date, signature, post so both pages visible if two pages result, make rules clear, appropriate and enforced.

10 days

6-18-04

Reyes

Raftery

4152

alcohol

Alcoholic beverages are stored in this area, or evidence of consumption. Remove/dispose alcoholic beverage bottles.

immed

    4-14-04

Reyes

Ramachandran

222

postdoor

Emergency telephone numbers (24 hours) must be posted on outside of lab door(s). See http://www.purdue.edu/rem/home/forms/DOORPOST.DOC

10 days

4-18-04

Garner

Ramachandran

5125

flamcab

Excess flammables stored outside of approved cabinet and/or safety cans, or cabinet malfunctioning, improperly configured, or not kept closed. Flammable waste container exceeds 10 gallons.

60 days

4-18-04

Garner

Ramachandran

5125

labels

Container of chemical is unlabeled. Many wash bottles are without contents and hazards labels.

immed

4-12-04

Garner

Ramachandran

5125

hazasstailor

Hazard assessment certification is posted but is not appropriate to this work area. Remove WELDING and any other sections not necessary. Ensure that rules are clear, appropriate and enforced.

10 days

4-16-04

Garner

Ramachandran

5125

acronyms

Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See http://www.purdue.edu/rem/home/booklets/Acronyms.xls

immed

4-12-04

Garner

Ramachandran

5125

fraycord

Power cord damaged or broken. Electrical tape is unacceptable. The multiple outlet bar located near the Mettler P1200N balance has a power cord that is broken throughout its length.

10 days

4-18-04

Garner

Ramachandran

5125

egress

Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. A box blocks the north emergency exit door.

immed

4-5-04

Garner

Ramachandran

5135

hazasstailor

Hazard assessment certification is posted but is not appropriate to this work area. Remove WELDING and any other sections not necessary. Ensure that rules are clear, appropriate and enforced.

10 days

4-16-04

Garner

Ramachandran

5135

acronyms

Containers of chemicals are inadequately labeled. If acronyms, formulae, or abbreviations are used, post a legend/key near inside of entrance to room. See http://www.purdue.edu/rem/home/booklets/Acronyms.xls

immed

4-5-04

Garner

Ramachandran

5135

eyelevel

Display written SOP for accessing extremely high containers of liquids, or move containers of liquids stored above eye level to eye level or below.

30 days

4-18-04

Garner

Ramachandran

5135

fraycord

Power cord damaged or broken. Electrical tape is unacceptable. Heat mantle's power cord is broken and taped, hood D.

10 days

4-5-04

Garner

Regnier

3174B

egress

Means of egress are obstructed or impeded by item(s) in or across walkway or corridor. (Access to 3174C)

5-25-04

 

Seeley

Regnier

3184

labels

Container of chemical is unlabeled.

5-10-04

  Seeley

Santini

073

machineguard

Machine guard is missing. Bridgeport mill is without a chuck guard

5-16-04

PPE sign will be installed by July 1, 2004

Everly

Santini

073

machineguard

Machine guard is missing. Lathe is without a chuck guard.

5-16-04

PPE sign will be installed by July 1, 2004 Everly

Santini

073

machineguard

Machine guard is missing. Delta drill press is without a chuck guard.

5-16-04

PPE sign will be installed by July 1, 2004

Everly

Santini

075

machineguard

Machine guard is missing. Monarch lathe is without a chuck guard.

5-16-04

PPE sign will be installed by July 1, 2004

Everly

Santini

075

machineguard

Machine guard is missing. Large Monarch lathe is without a chuck guard.

5-16-04

PPE sign will be installed by July 1, 2004

Everly

Santini

075

machineguard

Machine guard is missing.Johanson drill press is without a chuck guard.

5-16-04

PPE sign will be installed by July 1, 2004

Everly

Santini

075

misc

Flash back and back flow preventers needed on oxygen and acetylene tanks after the regulators.

5-16-04

flash-back hardware will beordered ASAP

Everly

Santini

075

grinder

Craftsman pedestal grinder is without tongue guards adjusted to no more than 1/4" clearance above the abrasive wheels.

5-16-04

GUARDS WILL BE ADDED AND ADJUSTED AS NEEDED

Everly

Santini

081

genduty

Workplace not reasonably free of recognized hazards. An 18"x12" piece of asbestos needs to be removed from the workplace. Contact Kevin Thedans phone 61937 to arrange for its removal.

5-16-04

Thedans will be asked to remove asbestors ASAP

Everly

Santini

4151A

housekeep

Restore housekeeping. (Sweep up small amount of metal turnings on floor in corner.)

5-16-04

Complete cleanup by June 11, 2004

Everly

secretary

4150

fraycord

Power cord damaged or broken at plug. East wall, cord goes up into ceiling to unknown location.

10 days

6-5-04

Dirksen

Skrynnikov

333D

opencont

Open chemical containers not in use.

immed

5-20-04 Simon

Skrynnikov

333E

openwaste

Open chemical waste containers not in use.

immed

5-20-04 Simon

Skrynnikov

345A

labels

Container of chemical is unlabeled.

immed

5-20-04 Simon

Vacant

101

electricspace

Minimum clear space of 36 '' not maintained in front of switchboard. Safety switch on south wall is obstructed.

10 days

6-14-04

Swihart

Vacant

101

electricspace

Minimum clear space of 36 '' not maintained in front of switchboard. Safety switch in SSE corner is obstructed

10 days

6-14-04

Swihart

Vacant

101B

combuststorage

Combustible materials not stored safely. More than 25 large empty cardboard boxes need to be removed or collapsed for storage.

immed

6-14-04

Swihart

Wei

413

labels

Containers of chemical unlabeled -- unattended flasks in hoods C, G. Check all areas.

immed

5-14-04

Jean

Wei

413

fraycord

Power cord damaged or broken. Pump in hood C

10 days

5-14-04

Jean

Wei

413

chemhousekeep

Chemical spills anywhere must be cleaned up immediately. See hoods D, G.

10 days

5-14-04

Jean

Wei

413

hoodcrowd

Chemical hood unsafe due to storage of flammable liquid containers in same area where chemical reactions performed and sources of heat and/or sparks exist..

10 days

5-14-04

Jean

Wei

440

flamcab

Excess flammables stored outside of approved cabinet and/or safety cans.

60 days

5-14-04

Jean

Wood

144

electricspace

Minimum clear space of 36 '' not maintained in front of switchboard. Two electrical safety switches in the NE corner of the room are obstructed.

10 days

P-59 submitted 5/4/04 - Complete as of 6-17-04

Wood

Wood/Lipschutz

145, in corridor

electricspace

Minimum clear space of 36 '' not maintained in front of switchboard.

10 days

5-5-04

Wood

  ***** The alarms in the glass lab are still in progress.  P-59 complete, cost for new full circuit will be $2000, and Central Shops has not scheduled it yest due to staff changes but as of 10/25/04 it should be at or near the top of their list.